Skip Navigation
This table is used for column layout.



Click here to visit the City of Rockledge Buy Local Portal

Click for Rockledge, Florida Forecast
Flooded Suction Can Lift Station Technical Specification
Site
Station Foundation and Wetwell
Can Station
Control Panel


**Note:  Submersible lift stations will carry a maximum of 200 GPM and 10 HP pumps.  Anything greater will require a dry pit flooded suction can station.  

Calculation:  Units x 350 Gal. X 2.5 /1440 = GPM

LIFT STATION SITE:

  • Minimum 75’ x 75’ site deeded to City of Rockledge with minimum 40’ x 40’ fenced area around station (commercial and industrial:  only 40’ x 40’ fenced area must be deeded, remainder of the site to be easement)
  • Property corners identified with concrete markers
  • Site elevation:  12’ above finished road grade
  • Fence:  6’ high, 9 ga. fabric, 3-strand barbed, 4’ walk gate, 12’ double drive gate, standard weight post, top rail, 7 ga. wire on bottom with hog rings (residential:  fencing as required for security and aesthetics, with minimum stated)
  • Site (75’ x 75’) sodded, other shall be seed and mulch, landscaped for buffer screening.  Oleander and/or hibiscus around outside of fenced area 4’ from fence on 6’ centers
  • Access road – concrete (min. 5” wire reinforced) , Asphalt – same spec as roadway
  • Potable water supply
  • Underground electrical service
  • Drainage as per City of Rockledge code
STATION FOUNDATION AND WET WELL:

  • 10’ x 12’ x 1’ concrete slab (allowed to set for 48 hours) with 5/8” reinforcement rods in slab every 6”, welded together (footer for can).  
  • Tie-down rods bent over I-beams, encased in slab and cemented over to about 8” to 10” up the side of the can.  
  • 16’ x 20’slab to be poured 6” thick around wet and dry wells
  • Entrance tube shall be 18” to 20” above slab
  • Entrance tube should act as guide and centered with 6’ of freeboard on all sides
  • 8’ diameter wet-well minimum
  • 4’ square aluminum hatch cover with stainless steel hardware
  • 4” PVC vent pipe
  • Can 4’ to 5’ from wet-well
  • Detail of emergency hydraulic hook-up
  • Aluminum hatch cover for basket
  • 8’ diameter wet-well precast, minimum
  • Minimum wall thickness:  8” (minimum 12” for wells over 25’ deep)
  • Bottom slab will be 17’ x 14’ with #5 rebar on 6” center protruding out of the slab 36”, a cast keyway 14’ x 9” x 3” with #5 rebar on 12” center extending into and protruding out of slab 36”  
  • Top elevation:  12” above finished road grade
  • All holes located within 12” of the top of the riser
  • Two (2) coats of Kopper Bitumastic 300m epoxy resin inside and out, one coat to be applied in the field (white)
  • Stainless steel, aluminum or fiberglass rag basket, situated to facilitate removal for cleaning rail system winch assembly for basket removal
CAN STATION:

  • Discharge pressure gauges on lines
  • Florescent light over sump area
  • Welded rung ladder, with anti-slip compound
  • Bell & Gossett air compressor, with tank
  • 4 anodes, 17# magnesium
  • Sump discharge line from dry well to extend within 12” of top of station, before discharging into wet well
  • Motors shall be steel, not aluminum
  • “Celery” green paint, inside of can
  • 9’-9” diameter station
  • Plug valves on discharge and suction
  • Stainless steel disconnect
  • ENPO sump pump, model AV or Sprint II model 4C445
  • Dayton shaded pole blower, model 2C946
  • Full operation maintenance and lube schedules, parts list and instructions
  • Check valves to have lever and spring
  • Provide a spare mechanical seal
  • Provide touch-up paint
  • Dark green paint on outside of can
CONTROL PANEL:

  • Panel on side of can, not in front of pumps
  • Florescent light over panel
  • Wet well level gauge
  • High/low level alarm lights, with guard
  • Phase loss protection (to have a double pole monitor, one is for Compucom telemetry)
  • Lightning arrestors
  • Surge arrestors
  • Honeywell pressure
  • ALLEN-BRADLEY H-O-A switches
  • ALLEN-BRADLEY manual alternator
  • ALLEN-BRADLEY starters (reduced voltage part winding)
  • WESTINGHOUSE circuit breakers
  • Elapsed time meters
  • Manual control
  • Telemetry system (Compucom, Inc.)
  • 15’ high, 1” diameter galvanized pie for antenna (to be bracketed to utility pedestal)
  • Emergency generator receptacle
NOTES:  
All materials and equipment are to be approved by the City of Rockledge and comply with their specifications.

Backfill materials over the bottom slab shall be compacted to 95% maximum density for the full depth of backfill.  


City of Rockledge 1600 Huntington Ln., Rockledge, FL 32955 PH: (321) 690-3978 FAX: (321) 690-3987
Website Disclaimer      Virtual Towns & Schools Website